PRODUCTS
SPECIFICATION
1.
MAJOR DIFFERENCES BETWEEN UNET AND STANDARDS
- Standards
provide performance requirements for the components and the link
without specifying or identifying a matched system. UNET tests
components and channels and can explain how the components will
work together as a system.
- Standards
allow for impedance smoothing; UNET does not.
- UNET's
patch cord specs include both return loss and NEXT.
- UNET
won't accept splices or non-virgin materials.
- UNET
requires power sum testing for connecting hardware (as well as
for cable and channel), while the standards do not.
|
|
TIA
Cat 5
TIA-568A Oct-95 (Obsolete)
|
TIA
Cat 5E
TIA-568B May-01
|
TIA
Cat 6 Draft 8
May-01
|
ALC
6
R17.00L
Nov-00
|
ALC
7
R17.00L
Nov-00
|
UNET
R3.00XP
Nov-00
|
UNET
R3.00XP
Nov-00
|
|
Maximum
Test Frequency
|
100
MHz
|
100
MHz
|
250
MHz
|
250
MHz
|
350
MHz
|
250
MHz
|
350
MHz
|
|
Passive
Testing @ 100 MHz:
|
|
|
|
(db)
|
(db)
|
(db)
|
(db)
|
(db)
|
(db)
|
(db)
|
|
Attenuation
(The lower the number, the better solution)
|
|
|
Cable
|
22.0
|
22.0
|
19.8
|
22.0
|
19.8
|
21.7
|
19.7
|
|
Connector
|
0.4
|
0.4
|
0.2
|
0.4
|
0.2
|
0.4
|
0.2
|
|
Channel
|
24.0
|
24.0
|
21.3
|
24.0
|
20.8
|
23.8
|
20.9
|
|
Power
Sum NEXT (The higher the number, the better solution)
|
|
|
Cable
|
N/A
|
32.3
|
42.3
|
34.3
|
43.3
|
34.3
|
44.3
|
|
Connector
|
N/A
|
N/A
|
50.0
|
41.0
|
50.0
|
41.0
|
50.0
|
|
Channel
|
N/A
|
27.1
|
37.1
|
28.6
|
37.6
|
28.6
|
37.6
|
|
Power
Sum ACR (The higher the number, the better solution)
|
|
|
Cable
|
N/A
|
N/A
|
22.5
|
12.3
|
23.5
|
12.6
|
23.6
|
|
Channel
|
N/A
|
N/A
|
15.8
|
4.6
|
16.8
|
4.9
|
16.8
|
|
Power
Sum ELFEXT (The higher the number, the better solution)
|
|
|
Cable
|
N/A
|
20.8
|
24.8
|
23.8
|
25.8
|
23.8
|
25.8
|
|
Connector
|
N/A
|
N/A
|
40.1
|
34.0
|
40.1
|
34.0
|
40.1
|
|
Channel
|
N/A
|
14.4
|
20.3
|
16.8
|
20.8
|
16.8
|
20.8
|
|
Return
Loss (The higher the number, the better solution)
|
|
|
Cable
|
15.0
|
20.1
|
20.1
|
20.1
|
20.1
|
21.5
|
22.5
|
|
Connector
|
14.0
|
20.0
|
24.0
|
20.0
|
24.0
|
21.0
|
24.0
|
|
Channel
|
N/A
|
10.0
|
12.0
|
10.0
|
12.0
|
12.0
|
14.0
|
2.
QUICK OVERVIEW: COMPARE XP LEVELS TO THE OTHERS
|
|
TIA/EIA
Cat 5E
|
Other
Programs
|
UNET
|
|
Tested
for:
|
|
|
Attenuation
|
V
|
V
|
V
|
|
NEXT
|
V
|
V
|
V
|
|
Power
Sum ACR
|
V
|
V
|
V
|
|
Return
Loss
|
|
|
V
|
|
Purchasing
Specification
|
|
|
V
|
|
All
Manufacturers Must Meet ISO 9001
|
|
|
V
|
|
Inventory
Not Compliant Is Sent Back To Manufacturer
|
|
|
V
|
|
Cable
Cannot Have Any Splices
|
|
|
V
|
|
Exceeds:
|
|
|
ANSI/ICEA
5-90-661
|
|
|
V
|
|
CSA
|
|
|
V
|
|
UL
444
|
|
|
V
|
|
ANSI/TIA/EIA
568-A
|
|
|
V
|
|
ISO/IEC
11801
|
|
|
V
|
|
CENELEC
EN50173: 1995
|
|
|
V
|
|
NEC
NFPA70
|
|
|
V
|
|
NEMA
NFPA 70
|
|
|
V
|
|
NEMA
WC-63/66
|
|
|
V
|
|
Use
Only Virgin Materials
|
|
|
V
|
|
Testing
Components Since 1988
|
|
|
V
|
|
Component
Tested
|
|
|
V
|
|
Channel
Tested
|
|
|
V
|
|
Tested
& Tuned to Work Together
|
|
|
V
|
|
Patch
Cords Tested
|
|
|
V
|
|
Input
Impedence Measured Per ASTM 4566-94, 43.2 Method 2, Option 2
|
|
|
V
|
|